{ "schema_version": "1.4.0", "id": "GHSA-wg4m-r562-77pw", "modified": "2022-04-13T00:01:11Z", "published": "2022-02-10T00:00:29Z", "aliases": [ "CVE-2021-40363" ], "details": "A vulnerability has been identified in SIMATIC PCS 7 V8.2 and earlier (All versions), SIMATIC PCS 7 V9.0 (All versions), SIMATIC PCS 7 V9.1 (All versions < V9.1 SP1), SIMATIC WinCC V15 and earlier (All versions), SIMATIC WinCC V16 (All versions < V16 Update 5), SIMATIC WinCC V17 (All versions < V17 Update 2), SIMATIC WinCC V17 (All versions >= V17 Update 2), SIMATIC WinCC V7.4 and earlier (All versions), SIMATIC WinCC V7.5 (All versions < V7.5 SP2 Update 6). The affected component stores the credentials of a local system account in a potentially publicly accessible project file using an outdated cipher algorithm. An attacker may use this to brute force the credentials and take over the system.", "severity": [ { "type": "CVSS_V3", "score": "CVSS:3.1/AV:L/AC:L/PR:L/UI:N/S:U/C:H/I:H/A:H" } ], "affected": [], "references": [ { "type": "ADVISORY", "url": "https://nvd.nist.gov/vuln/detail/CVE-2021-40363" }, { "type": "WEB", "url": "https://cert-portal.siemens.com/productcert/pdf/ssa-914168.pdf" } ], "database_specific": { "cwe_ids": [ "CWE-312", "CWE-538" ], "severity": "HIGH", "github_reviewed": false, "github_reviewed_at": null, "nvd_published_at": "2022-02-09T16:15:00Z" } }