{ "schema_version": "1.4.0", "id": "GHSA-g3r4-3cw9-j3p7", "modified": "2022-05-13T01:53:18Z", "published": "2022-05-13T01:53:18Z", "aliases": [ "CVE-2018-7246" ], "details": "A cleartext transmission of sensitive information vulnerability exists in Schneider Electric's 66074 MGE Network Management Card Transverse installed in MGE UPS and MGE STS. he integrated web server (Port 80/443/TCP) of the affected devices could allow remote attackers to discover an administrative account. If default on device, it is not using a SSL in settings and if multiple request of the page \"Access Control\" (IP-address device/ups/pas_cont.htm) account data will be sent in cleartext", "severity": [ { "type": "CVSS_V3", "score": "CVSS:3.0/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H" } ], "affected": [], "references": [ { "type": "ADVISORY", "url": "https://nvd.nist.gov/vuln/detail/CVE-2018-7246" }, { "type": "WEB", "url": "https://www.schneider-electric.com/en/download/document/SEVD-2018-074-01" } ], "database_specific": { "cwe_ids": [ "CWE-319" ], "severity": "CRITICAL", "github_reviewed": false, "github_reviewed_at": null, "nvd_published_at": "2018-04-18T20:29:00Z" } }