{ "schema_version": "1.4.0", "id": "GHSA-hw79-77g6-22xq", "modified": "2022-05-20T00:00:37Z", "published": "2022-05-11T00:01:41Z", "aliases": [ "CVE-2021-41545" ], "details": "A vulnerability has been identified in Desigo DXR2 (All versions < V01.21.142.5-22), Desigo PXC3 (All versions < V01.21.142.4-18), Desigo PXC4 (All versions < V02.20.142.10-10884), Desigo PXC5 (All versions < V02.20.142.10-10884). When the controller receives a specific BACnet protocol packet, an exception causes the BACnet communication function to go into a “out of work” state and could result in the controller going into a “factory reset” state.", "severity": [ { "type": "CVSS_V3", "score": "CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H" } ], "affected": [], "references": [ { "type": "ADVISORY", "url": "https://nvd.nist.gov/vuln/detail/CVE-2021-41545" }, { "type": "WEB", "url": "https://cert-portal.siemens.com/productcert/pdf/ssa-662649.pdf" } ], "database_specific": { "cwe_ids": [], "severity": "HIGH", "github_reviewed": false, "github_reviewed_at": null, "nvd_published_at": "2022-05-10T11:15:00Z" } }